ArIEC103 Troubleshooting Guide

This document focuses on practical IEC-103 field symptoms and likely checks.

No response from relay

Check in this order:

  1. Confirm the COM port is correct.
  2. Confirm baudrate, parity, data bits, and stop bit.
  3. Confirm IEC-103 link address.
  4. Confirm common address.
  5. Confirm RS-485 A/B polarity.
  6. Confirm only one master is active on the serial segment.
  7. Try startup with Reset FCB enabled.
  8. Increase timeout for the first test.
  9. Check TX counter: if TX is zero, the session is not sending.
  10. Check RX activity: if RX is zero, suspect wiring, adapter, port, or relay setting.

Many checksum errors

Likely causes:

  • wrong baudrate;
  • wrong parity;
  • noisy serial wiring;
  • bad USB-to-serial or RS-485 adapter;
  • missing or unsuitable termination;
  • serial line shared with another active master.

Recommended action:

  • validate the physical layer first;
  • reduce cable length for bench test;
  • use a known-good adapter;
  • verify relay serial settings from its front panel or configuration file.

Malformed frames or random bytes

Likely causes:

  • wrong serial settings;
  • noise or half-duplex direction issue;
  • adapter driver problem;
  • another device transmitting on the line.

ArIEC103 attempts to resynchronize the FT1.2 stream after noise bytes, but persistent malformed traffic should be treated as a physical-layer or serial-setting problem first.

Relay answers once, then stops

Possible causes:

  • wrong link state after previous master activity;
  • relay expects a clean reset sequence;
  • timeout too aggressive;
  • FCB sequence recovery needed after communication errors.

Recommended action:

  • enable Reset FCB at startup;
  • run a short test with conservative timeout;
  • disconnect other masters;
  • stop and restart the session after confirming address/settings.

General Interrogation does not complete

Check:

  • relay supports GI on the configured address;
  • common address is correct;
  • timeout and GI follow-up limits are not too low;
  • Diagnostics tab for DFC busy, timeout, or malformed responses.

Class 1 events are not visible

Remember: Class 1 is event/high-priority data. It should not be hammered continuously.

Check:

  • whether the relay actually advertises ACD=1;
  • whether a real event was generated;
  • whether GI follow-up is bounded too tightly;
  • whether the relay event is mapped or only visible as raw FUN/INF.

Values appear but names are not readable

This is usually a mapping issue, not a protocol failure.

Check:

  • mapping profile is loaded;
  • FUN/INF values match the relay/project signal list;
  • state map contains expected DPI/value values;
  • unmapped rows still show raw FUN/INF protocol evidence.

Evidence report contains unexpected information

Before sharing outside the project team:

  • review project names;
  • review relay address and serial settings;
  • review raw frame evidence;
  • review mapping profile file names;
  • remove customer-sensitive comments if added manually.

Public evidence export is designed to avoid full local workstation paths by default, but engineering evidence can still contain project-specific information.